After the configuration, the H831VESC works in the normal
state and monitors the digital parameters set on the MA5620 /MA5626 . When the
actual level of a monitored digital parameter is different from the valid level
preset in the system, the MA5620/MA5626 reports an alarm.
huawei(config)#emu add 3 MINIESC 0 8 RS232 MiniESC
huawei(config)#interface emu 3
huawei(config-if-miniesc-3)#esc analog 0 alarm-upper-limit
54 alarm-lower-limit 6
Send command to
environment monitor board ,please waiting for the ack
huawei(config-if-miniesc-3)#
Execute command
successful
huawei(config-if-miniesc-3)#esc analog 2 alarm-upper-limit
75 alarm-lower-limit
5 name humidity sensor-type 0:voltage analog-alarm 2 unit
%RH
Send command to
environment monitor board ,please waiting for the ack
huawei(config-if-miniesc-3)#
Execute command
successful
huawei(config-if-miniesc-3)#esc digital 1 available-level
high-level
digital-alarm 8 name Door0
Send command to
environment monitor board ,please waiting for the ack
huawei(config-if-miniesc-3)#
Execute command
successful
huawei(config-if-miniesc-3)#esc digital 2 available-level
low-level
digital-alarm 11 name Fan
Send command to
environment monitor board ,please waiting for the ack
huawei(config-if-miniesc-3)#
Execute command
successful
huawei(config-if-miniesc-3)#display esc environment
info
EMU ID: 3 ESC environment
state
---------------------------Analog environment
info--------------------------
ID Name State Value
AlmUpper AlmLower Unit
0 Temperature Normal 30.00
54 6 C
1 Input_-48V_0 Normal
54.00 60 45 Volt
2 Humidity Low -128.00
75 5 %RH
3 - Normal -128.00
127 -128 -
---------------------------Digital environment info-------------------------
ID Name State Value |ID Name State Value
0 Wiring Normal 1 |1
Door0 Alarm 0
2 Fan Normal 0 |3
- Normal 1
4 - Normal 1 |5
- Normal 1
6 - Normal 1 |7
- Normal 1
8 Fog Normal 1 |9
Water_Alarm Normal 1
----------------------------------------------------------------------------
huawei(config-if-miniesc-3)#quit
huawei(config)#save